Product Description
The ZED-TID-M drill is a battery supplied device which can measure at the same time the temperature of 2 NTC sensors and the status of 2 digital input and regularly send the collected information toward a 4-noks range Gateway.
Is possible to set the device in order to manage alarms to ring when its limits are trespassed, because of a too high or too low temperature. Is possible to set the device in order to manage alarms to ring when its limits are trespassed, because of a too high or too low temperature.
The device can transmit automatically and immediately (out of the sampling time you have set up) also for a status change of one of the two input.
Technical Specs | |
---|---|
General characteristics |
Chip Ember EM250
Compatible IEEE 802.15.4 Stack EmberZnet 3.5.x (ZigBee PRO) Modbus/RTU Address settable through internal dip-switch Wall-mounting with screws Cable gland: PG9 |
RF characteristics | Frequency: 2405 MHz ÷ 2480 MHz Modulation: DSSS Nominal transmission power: 2mW (3 dBm) Receiver sensitive: -95 dBm Internal antenna gain: 0 dB Outdoor/indoor range: 100m/30m |
Supply | High Energy Density AA 3,6V/2000mAh Lithium Battery Battery duration: 3 years for data transmission every minute at 20°C |
Inpur for NTC drill |
NTC type drill
103AT Type (R25 = 10 KOhm; Beta = 3435K) Measurement range: -50°C ÷ +100°C Reading resolution: 0,1°C
Reading accuracy: ±1,0°C Temperature measurements expressed as tenths of degree |
Digital Input |
Non-isolated input for clean contact
Closure electrical current 0,01mA. Use self cleaning contacts
|
Connection | Plug off morsels (3,81 mm pitch) |
Environment Parameters | Operating temperature: -10 ÷ +60°C; <80% U.R. non condensing Storage temperature: -20 ÷ +70°C; <80% U.R. non condensing Degree of protection: IP 55 |
Compliant with 2006/95/EEC, 89/336/EEC, 99/5/EEC directives
Product law applied
|
ETSI EN 300 328: Radio Compatibility for digital wide band transmissions ETSI EN 301 489: Radio Compatibility EN 61000-6-2: Electromagnetic Compatibility – Emissions EN 61000-6-3: Electromagnetic Compatibility – Immunity EN 60950-1: Electric Security |