Product Description
The ZR-HMETER.W-M is a meter for electric energy and is part of the ZB-Connection range. It includes a 70 Amp power transformer to measure the real power up to 50 kW and has an energy counter. Moreover, it has a digital outout to pilot a high power external relay. Moreover is available stand-by killer and override button functions. You can set a power limit under which the device is meant to be in stand-by killer mode and so the external relay can be automatically turned off. With the override button the user can override the last command from the Gateway. Such tasks are carried out after simple Modbus commands sent to ZB-Connection network that transform them in wireless command. The device is continuously supplied by a 230 Vca output, so it can also work as a repeater or a “father” device for battery supplied sensors.
Technical Specs | |
---|---|
General characteristics |
Chip Ember EM357 Compatible IEEE 802.15.4 Stack EmberZnet473 (ZigBee PRO) Modbus/RTU Device address settable via internal dip-switch
|
RF characteristics | Frequency: 2405 MHz ÷ 2480 MHz Modulation: DSSS Nominal transmission power: 10mW (10 dBm) Reception sensitivity: 103 dBm External antenna gain: 5,5 dB Coverage outdoor/indoor: 200m/50m |
Supply | 230 Vdc |
Measurement |
Double three-phase electric power systems or six single-phase electric power systems
|
Connections | DIN rail. Available in 6 DIN module size 105x110x60 mm Voltage current, active power, reactive power, active energy, reactive energy |
Antenna | External antenna |
Environment Parameters | Operating temperature: 0°C ÷ +50°C; <80% U.R. not condensing Storage temperature: -20 °C÷ +70°C; <80% U.R. not condensing Degree of protection: IP 30 |
Compliant with 2006/95/EEC, 89/336/EEC, 99/5/EEC directives
Product law applied
|
ETSI EN 300 328: Radio Compatibility for digitals wide band transmissions ETSI EN 301 489: Radio Compatibility EN 55014-1:2006 + A 1:2009: Electromagnetic Compatibility – Immunity EN 61000-3-2:2006: Electromagnetic Compatibility – Emissions EN 61000-3-3:2008: Electromagnetic Compatibility – Emissions EN 55014-2: Electromagnetic Compatibility – Immunity |
Reviews
There are no reviews yet.